product or component type: Circuit breaker
device application: Distribution
poles description: 3P
protected poles description: 3t
network type:
DC
AC
network frequency: 50/60 Hz
[In] rated current: 100 A at 40 °C
[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2
[Ue] rated operational voltage:
550 V AC 50/60 Hz conforming to IEC 60947-2
250 V DC conforming to IEC 60947-2
breaking capacity code: B/N
suitability for isolation: Yes conforming to IEC 60947-2
utilisation category: Category A
trip unit name: TM-D
trip unit technology: Thermal-magnetic
trip unit rating: 100 A at 50 °C
Protection type:
Short-circuit protection
Overload protection
Pollution degree:
3 conforming to IEC 60664-1
3 conforming to IEC 947-1
Complementary:
control type: Toggle
mounting mode: Fixed
mounting support: Backplate
upside connection: Front
downside connection: Front
mechanical durability: 8500 cycles
electrical durability: Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2
connection pitch: 25 mm
local signalling: Positive contact indication
neutral protection setting: Without protection
earth-leakage protection: Without
height: 130 mm
width: 75 mm
depth: 60 mm
Reviews